M-SYSTEMS Industrial Partner

M5CT - M-Systems M5CT M5-UNIT Series Terminal Block Signal Conditioner; CT Transmitter...

larger image

Request Quote
For Price
Part Number:
M5CT
Model Number:
M5CT
Make:
M-SYSTEMS
Lead Time:
Available
Qty In Stock:
Available

M-Systems M5CT M5-UNIT Series Terminal Block Signal Conditioner; CT Transmitter Simple Type: Signal Conditioning

Signal conditioners convert a field signal from various sensors into standard signal suitable for processing in PLC, DCS or PC-based systems. They are also used to boost a signal to increase load drive capability, to isolate a signal to stop ground loops. More than 75000 combinations of process signal I/O, power input and mounting configuration are selectable. Additionally, M-System offers the broadest line of signal splitters available. M5 Series Transmitters are designed to accept a wide variety of process signal input and provide a standard and non-standard DC output.

Download the datasheet (PDF)

For Resellers and High Volume Orders:
Please request a quote to obtain preferred pricing.

Features

  • 2000V AC isolation (1500V AC for AC powered)
  • CE marking for 24 V DC power
  • Converts an alternating current from a current transformer into a standard process signal
  • High-density mounting
  • Only 41 mm (1.61 in") deep modules can be installed anywhere, even behind the panel cover
  • Power indicator LED
  • Selectable power input 24V DC, 85–264V AC
  • Standard DIN rail mounting
  • The M5 Series features single channel four-wire models
  • True RMS sensing

Specifications

    General
  • AC Power Consumption: Approx. 2 VA at 100 V; Approx. 3 VA at 200 V; Approx. 3 VA at 264 V
  • Accuracy: ±0.3 % with input 5 – 100 % (Input 10 – 100 % for the output codes 4W and 5W)
  • Connection: M3.5 screw terminals (torque 0.8 N•m)
  • Construction: Terminal block
  • DC Power Consumption: Approx. 2 W
  • Dielectric strength (input to output to power to ground): DC powered: 2000 V AC @1 minute; AC powered: 1500 V AC @1 minute
  • Housing material: Flame-resistant resin (black)
  • Insulation resistance: Greater than or equal to 100 M Omega with 500 V DC
  • Isolation: Input to output to power
  • Line voltage effect: ±0.1 % over voltage range
  • Mounting: DIN rail
  • Operating humidity: 0 to 90 %RH (non-condensing)
  • Operating temperature: -5 to +55°C (23 to 131°F)
  • Power LED: Green light turns on when the power is supplied.
  • Response time: Less than or equal to 0.5 sec. (0 – 90 %)
  • Ripple: 0.5 %p-p max
  • RMS sensing: Up to 15 % of 3rd harmonic content
  • Screw terminal: Nickel-plated steel
  • Span adjustment: 98 to 102 % (front)
  • Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
  • Weight: 80 g (2.8 oz)
  • Zero adjustment: -2 to +2 % (front)

 

Applications

  • None Available

Aliases