M-Systems M3SXV M3S-UNIT Series Space-saving Signal Conditioner; Signal Transmitter (PC Programmable) Simple Type: Signal Conditioning

Signal conditioners convert a field signal from various sensors into standard signal suitable for processing in PLC, DCS or PC-based systems. They are also used to boost a signal to increase load drive capability, to isolate a signal to stop ground loops. More than 75000 combinations of process signal I/O, power input and mounting configuration are selectable. Additionally, M-System offers the broadest line of signal splitters available. This thin profile M3S-Unit Series is a signal conditioner has universal AC/DC power input models available.

Download the datasheet (PDF)

For Resellers and High Volume Orders:
Please request a quote to obtain preferred pricing.

Features

  • CE marking
  • Converts a DC input into a standard process signal
  • DC input model with optional fast response time
  • High-density mounting
  • PC programmable models available
  • Power and status indicator LED
  • Super-space-saving 12mm (0.47") width
  • Universal AC/DC power input

Specifications

    General
  • AC Power Consumption: Approx. 2 VA at 100 V; Approx. 3 VA at 200 V; Approx. 4 VA at 264V
  • Applicable wire size: 0.2 to 2.5 mm2
  • Configurator connection: 2.5 dia. miniature jack; RS-232-C level
  • Connection: Removable terminal block
  • Construction: Small-sized front terminal structure
  • DC Power Consumption: R-Approx. 0.5 W; AD-Approx. 1 W
  • Dielectric strength: 2000 V AC @1 minute (input to output to power to ground)
  • Housing Material: Flame-resistant resin (gray)
  • Input accuracy: (% of max. input range) -1000 – +1000 mV : ±0.01%; -10 – +10 V : ±0.01%; 0 – 50 mA : ±0.02%
  • Insulation resistance: Greater than or equal to 100 M Omega with 500 V DC
  • Isolation: Input to output to power
  • Line voltage effect: ±0.1 % over voltage range
  • Mounting: DIN rail
  • Operating humidity: 30 to 90 %RH (non-condensing)
  • Operating temperature: -10 to +55°C (14 to 131°F)
  • Output accuracy: ±0.04 % of max. output range
  • Over-range output: -2 – +102 % (Negative current output is not available.)
  • Overall accuracy: Input accuracy + output accuracy (Inversely proportional to the span.)
  • Power Led: Green light turns on when the power is supplied.
  • Programming: Downloaded from PC; input type and range, output type and range, zero and span, user’s linearization table (max. 101 points, specified within -2 to +102% for both input and output), etc.
  • Response time: Less than or equal to 0.5 sec. (0 – 90 %)
  • Span adjustment: 98 to 102 % (PC programming)
  • Status indicator LED: Orange LED; Flashing patterns indicate different operating status of the transmitter.
  • Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) of max. span
  • Weight: 85 g (3.0 oz)
  • Zero adjustment: -2 to +2 % (PC programming)

 