M3SXR - M-Systems M3SXR M3S-UNIT Series Space-saving Signal Conditioner; RTD Transmitter (PC...
Request Quote
For Price
- Part Number:
- M3SXR
- Model Number:
- M3SXR
- Make:
- M-SYSTEMS
- Lead Time:
- Available
- Qty In Stock:
- Available
M-Systems M3SXR M3S-UNIT Series Space-saving Signal Conditioner; RTD Transmitter (PC Programmable) Simple Type: Signal Conditioning
Signal conditioners convert a field signal from various sensors into standard signal suitable for processing in PLC, DCS or PC-based systems. They are also used to boost a signal to increase load drive capability, to isolate a signal to stop ground loops. More than 75000 combinations of process signal I/O, power input and mounting configuration are selectable. Additionally, M-System offers the broadest line of signal splitters available. This thin profile M3S-Unit Series is a signal conditioner that has universal AC/DC power input models available.
For Resellers and High Volume Orders:
Please request a quote to obtain preferred pricing.
Features
- Accepts direct input from an RTD and provides an isolated, linearized DC signal
- CE marking
- DC input model with optional fast response time
- High-density mounting
- Linearization and burnout protection
- PC programmable models available
- Power and status indicator LED
- Super-space-saving 12mm (0.47") width
- Universal AC/DC power input available
Specifications
- Applicable wire size: 0.2 to 2.5 mm2
- Burnout: Upscale standard; downscale or no burnout optional by programming
- Burnout response: Less than or equal to 10 sec
- Configurator connection: 2.5 dia. miniature jack; RS-232-C level
- Connection: Removable terminal block
- Construction: Small-sized front terminal structure
- Dielectric strength: 2000 V AC @1 minute (input to output to power to ground)
- Housing material: Flame-resistant resin (gray)
- Input accuracy: (whichever is greater)±0.1 % of FS or ±0.15°C (Pt and JPt); ±0.1 % of FS or ±1°C (Cu 10)
- Insulation resistance: Greater than or equal to 100 MO with 500 V DC
- Isolation: Input to output to power
- Line voltage effect: ±0.1 % over voltage range
- Linearization: Standard
- Mounting: DIN rail
- Operating humidity: 30 to 90 %RH (non-condensing)
- Operating temperature: -10 to +55°C (14 to 131°F)
- Output accuracy: ±0.04 % of max. Output range
- Over-range output: -2 – +102 % (Negative current output is not available.)
- Overall accuracy: Input accuracy + output accuracy
- Power Consumption AC: Approx. 2 VA at 100 V; Approx. 3 VA at 200 V; Approx. 4 VA at 264V
- Power Consumption DC: R: Approx. 0.5 W; AD: Approx. 1 W
- Power LED: Green light turns on when the power is supplied.
- Programming: Downloaded from PC
- Response time: Less than or equal to 1 sec. (0 – 90 %)
- Span adjustment: 98 to 102 % (PC programming)
- Status indicator LED: Orange LED; Flashing patterns indicate different operating status of the transmitter.
- Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) of max. span
- Weight: 85 g (3.0 oz)
- Zero adjustment: -2 to +2 % (PC programming)
Applications
- None Available
Aliases