M-Systems M2XUM Universal Transmitter PC Programmable; Modbus-RTU Communication Simple Type: Signal Conditioning

Signal conditioners convert a field signal from various sensors into standard signal suitable for processing in PLC, DCS or PC-based systems. They are also used to boost a signal to increase load drive capability, to isolate a signal to stop ground loops. M2 Series Signal Conditioners are designed to accept a largest range of process signal inputs and provide a standard and non-standard DC output.

Download the datasheet (PDF)

For Resellers and High Volume Orders:
Please request a quote to obtain preferred pricing.

Features

  • 2000V AC isolation
  • Base socket included with modules
  • CE marking and UL/C-UL Class 1 Div 2 approval (selected models)
  • Fixed range or PC programmable models selectable
  • Input and output ranges
  • M2 use a compact-size, plug-in socket base for quick installation or replacement of modules without disturbing wiring.
  • Selectable 100-240V AC/24V DC power input
  • Simulated output
  • Standard DIN rail or surface mounting
  • T/C and RTD type and temp. range
  • User's linearization table (max. 100 points, specified within -15 – +115 % for both input and output)
  • Zero and span adjustments

Specifications

    General
  • Burnout (T/C, RTD and Pot.): Upscale standard; downscale or no burnout options are PC programmable
  • Cold junction compensation (T/C): CJC sensor (included) to be attached to the input terminals
  • Configurator connection: 2.5 dia. miniature jack; RS-232-C level
  • Connection: M3 screw terminals (torque 0.8 N·m)
  • Construction: Plug-in
  • Housing material: Flame-resistant resin (black)
  • Isolation: Input to output to RS-485 to power
  • Linearization (T/C, RTD input): Standard tables stored in memory
  • Manual span adjustments: 95 to 105 % (factory setting
  • Manual zero adjustments: -5 to +5 % (factory setting
  • Over-range output: Approx. -15 to +115 % (Negative current output is not provided.)
  • Status indicator LED: Flashing patterns indicate different operating status of the transmitter.

 