M-Systems M2XPA2 Mini-M Series Super-mini Signal Conditioner; Frequency Transmitter (PC Programmable) Simple Type: Signal Conditioning

Signal conditioners convert a field signal from various sensors into standard signal suitable for processing in PLC, DCS or PC-based systems. They are also used to boost a signal to increase load drive capability, to isolate a signal to stop ground loops. More than 75000 combinations of process signal I/O, power input and mounting configuration are selectable. Additionally, M-System offers the broadest line of signal splitters available. M2 Series Signal Conditioners are designed to accept a largest range of process signal inputs and provide a standard and non-standard DC output.

Download the datasheet (PDF)

For Resellers and High Volume Orders:
Please request a quote to obtain preferred pricing.

Features

  • 2000V AC isolation
  • Base socket included with modules
  • CE marking and UL/C-UL Class 1 Div 2 approval (selected models)
  • Fixed range or PC programmable models selectable
  • M2 use a compact-size, plug-in socket base for quick installation or replacement of modules without disturbing wiring.
  • Selectable 100-240V AC/24V DC power input
  • Standard DIN rail or surface mounting

Specifications

    General
  • Accuracy: Input accuracy + output accuracy; Inversely proportional to the span
  • Connection: M3 screw terminals (torque 0.8 N-m)
  • Construction: Plug-in
  • Dielectric strength: 2000 V AC @1 minute (input to output to power to ground)
  • Housing Material: Flame-resistant resin (black)
  • Input accuracy: ±0.03 % of the selected freq. range
  • Isolation: Input to output to power
  • Line voltage effect: ±0.1 % over voltage range
  • Mechanical Contact Input amplitude: Min. 4 V, max. 12 V
  • Mechanical Contact Maximum frequency: 0 – 10 Hz
  • Mechanical Contact Sensing voltage / current: Approx. 12 V, 8 V or 4 V DC @1 mA
  • Open Collector Input amplitude: Min. 4 V, max. 12 V
  • Open Collector Maximum frequency: 0 – 100 kHz
  • Open Collector Sensing voltage/ current: Approx. 12 V, 8 V or 4 V DC @1 mA
  • Output accuracy: ±0.03 % of the selected output range
  • Over-range output: Approx. -15 to +115 % at 1 – 5 V
  • Pulse width time requirement: Min. 5 µsec., max. 10 sec
  • Response time: Ts + Td (0 – 90 %)
  • Span adjustment: 95 to 105 % (front)
  • Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) of I/O range at -5 to +55°C [23 to 131°F]
  • Voltage Pulse Detecting levels: -2 – +4V
  • Voltage Pulse Input amplitude: Min. 0.1 Vp-p, max. 100 Vp-p
  • Voltage Pulse Input impedance: 10 kO min.
  • Voltage Pulse Maximum frequency: 0 – 100 kHz
  • Voltage Pulse Waveform: Square or sine
  • Zero adjustment: -5 to +5 % (front)

 