M-SYSTEMS Industrial Partner

M2SP - M-Systems M2SP Mini-M Series Super-mini Signal Conditioner; Low Frequency Transmitter...

larger image

Request Quote
For Price
Part Number:
M2SP
Model Number:
M2SP
Make:
M-SYSTEMS
Lead Time:
Available
Qty In Stock:
Available

M-Systems M2SP Mini-M Series Super-mini Signal Conditioner; Low Frequency Transmitter (50 Hz minimum) Simple Type: Signal Conditioning

Signal conditioners convert a field signal from various sensors into standard signal suitable for processing in PLC, DCS or PC-based systems. They are also used to boost a signal to increase load drive capability, to isolate a signal to stop ground loops. More than 75000 combinations of process signal I/O, power input and mounting configuration are selectable. Additionally, M-System offers the broadest line of signal splitters available. M2 Series Signal Conditioners are designed to accept a largest range of process signal inputs and provide a standard and non-standard DC output.

Download the datasheet (PDF)

For Resellers and High Volume Orders:
Please request a quote to obtain preferred pricing.

Features

  • 2000V AC isolation
  • Base socket included with modules
  • CE marking and UL/C-UL Class 1 Div 2 approval (selected models)
  • Fixed range or PC programmable models selectable
  • M2 use a compact-size, plug-in socket base for quick installation or replacement of modules without disturbing wiring.
  • Selectable 100-240V AC/24V DC power input
  • Standard DIN rail or surface mounting

Specifications

    General
  • Accuracy: ±0.1 % (output 10 – 100 %)
  • Connection: M3 screw terminals (torque 0.8 N-m)
  • Construction: Plug-in
  • DC Current: 0 – 20 mA DC
  • DC VOLTAGE: 0 – 12 V DC
  • Dielectric strength: 2000 V AC @1 minute (input to output to power to ground)
  • Dry Contact: Mechanical contact or open collector
  • Excitation: 12 V DC @30 mA; short-circuit protection
  • FREQUENCY RANGE: 0 – 50 Hz through 10 kHz
  • Housing Material: Flame-resistant resin (black)
  • Input Filter: Provided with input range <100 Hz (time constant approx. 1 msec.)
  • Input impedance: 10 kO min
  • Input pulse sensing: DC coupled; detecting pulse rise
  • Isolation: Input to output to power
  • Line voltage effect: ±0.1 % over voltage range
  • Load resistance: Output drive 1 mA max.; at
  • Low-end cutout: 2 to 5 %
  • Minimum span: 5 mV
  • Offset: Max. 1.5 times span
  • Over-range output: 0 to 120 % at 1 – 5 V
  • Pulse width time requirement: 20 µsec. min. for high and low levels
  • Ripple: 0.2 %p-p max. with input
  • Sensing: Approx. 12 V DC @3 mA
  • Span adjustment: 95 to 105 % (front)
  • Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
  • Voltage Pulse: Square or sine waveforms
  • Zero adjustment: -5 to +5 % (front)

 

Applications

  • None Available

Aliases