M-SYSTEMS Industrial Partner

M2DU - M-Systems M2DU Mini-M Series Super-Mini Signal Conditioner; Current Loop Supply...

larger image

Request Quote
For Price
Part Number:
M2DU
Model Number:
M2DU
Make:
M-SYSTEMS
Lead Time:
Available
Qty In Stock:
Available

M-Systems M2DU Mini-M Series Super-Mini Signal Conditioner; Current Loop Supply (10-50mA loop) Simple Type: Signal Conditioning

Signal conditioners convert a field signal from various sensors into standard signal suitable for processing in PLC, DCS or PC-based systems. They are also used to boost a signal to increase load drive capability, to isolate a signal to stop ground loops. More than 75000 combinations of process signal I/O, power input and mounting configuration are selectable. Additionally, M-System offers the broadest line of signal splitters available. M2 Series Signal Conditioners are designed to accept a largest range of process signal inputs and provide a standard and non-standard DC output.

Download the datasheet (PDF)

For Resellers and High Volume Orders:
Please request a quote to obtain preferred pricing.

Features

  • 2000V AC isolation
  • Base socket included with modules
  • CE marking and UL/C-UL Class 1 Div 2 approval (selected models)
  • Fixed range or PC programmable models selectable
  • M2 use a compact-size, plug-in socket base for quick installation or replacement of modules without disturbing wiring.
  • Selectable 100-240V AC/24V DC power input
  • Standard DIN rail or surface mounting

Specifications

    General
  • AC Power input: Approx. 5 VA
  • Accuracy: ±0.1 %
  • Connection: M3 screw terminals (torque 0.8 N•m)
  • Construction: Plug-in
  • Current limited: 65 mA
  • Current rating: 55mA DC
  • DC Power input: Approx. 3 W
  • Dielectric Strength: 2000 V AC @1 minute (input to output to power to ground)
  • Housing Material: Flame-resistant resin (black)
  • Isolation: Input to output to power
  • Mounting: Surface or DIN rail
  • Operating humidity: 30 to 90 %RH (non-condensing)
  • Operating temperature: -5 to +55°C (23 to 131°F)
  • Output Signal: ±0.1 % over voltage range
  • Output voltage: 24 – 28 V DC with no load
  • Over-range output: Approx. -10 to +120 % at 1 – 5 V
  • Protected time duration: No limit
  • Span adjustment: 95 to 105 % (front)
  • Supply output: ±3 % over voltage range
  • TEMP COEFFICIENT: ±0.015 %/°C (±0.008 %/°F)
  • Weight: 150 g (0.33 lbs)
  • Zero adjustment: -5 to +5 % (front)

 

Applications

  • None Available

Aliases

  • None Available