M-SYSTEMS Industrial Partner

M2CA - M-Systems M2CA CT Transmitter (Average Sensing, RMS Calibrated Simple Type:...

larger image

Request Quote
For Price
Part Number:
M2CA
Model Number:
M2CA
Make:
M-SYSTEMS
Lead Time:
Available
Qty In Stock:
Available

M-Systems M2CA CT Transmitter (Average Sensing, RMS Calibrated Simple Type: Signal Conditioning

Signal conditioners convert a field signal from various sensors into standard signal suitable for processing in PLC, DCS or PC-based systems. They are also used to boost a signal to increase load drive capability, to isolate a signal to stop ground loops. More than 75000 combinations of process signal I/O, power input and mounting configuration are selectable. Additionally, M-System offers the broadest line of signal splitters available. M2 Series Signal Conditioners are designed to accept a largest range of process signal inputs and provide a standard and non-standard DC output.

Download the datasheet (PDF)

For Resellers and High Volume Orders:
Please request a quote to obtain preferred pricing.

Features

  • 2000V AC isolation
  • Base socket included with modules
  • CE marking and UL/C-UL Class 1 Div 2 approval (selected models)
  • Fixed range or PC programmable models selectable
  • M2 use a compact-size, plug-in socket base for quick installation or replacement of modules without disturbing wiring.
  • Selectable 100-240V AC/24V DC power input
  • Standard DIN rail or surface mounting

Specifications

    General
  • Connection: M3 screw terminals (torque 0.8 N-m)
  • Construction: Plug-in
  • DC Current: 0 – 20 mA DC
  • DC VOLTAGE: 0 – 12 V DC
  • Frequency: 50 or 60 Hz
  • Housing Material: Flame-resistant resin (black)
  • Input burden: 0.5 VA max.
  • Input burden: 0.5 VA max.Frequency
  • Isolation: Input to output to power
  • Load resistance: Output drive 1 mA max.; at = 0.5 V
  • Minimum span: 5 mV
  • Offset: Max. 1.5 times span
  • Operational range: 0 – 120 % of rating
  • Overload capacity: 200 % of rating for 1 minute, 120 % continuous
  • Overrange output: 0 to 120 % at 1 – 5 V
  • RMS sensing: Up to 15 % of 3rd harmonic content
  • Span adjustment: 95 to 105 % (front)
  • Zero adjustment: -5 to +5 % (front)

 

Applications

  • None Available

Aliases

  • None Available