20VS2-1 - M-Systems 20VS2-1 Hybrid Isolation Amplifiers 20 Series Isolation Amplifier (input...
Request Quote
For Price
- Part Number:
- 20VS2-1
- Model Number:
- 20VS2-1
- Make:
- M-SYSTEMS
- Lead Time:
- Available
- Qty In Stock:
- Available
M-Systems 20VS2-1 Hybrid Isolation Amplifiers 20 Series Isolation Amplifier (input isolation) Simple Type: Signal Conditioning
Signal conditioners convert a field signal from various sensors into standard signal suitable for processing in PLC, DCS or PC-based systems. They are also used to boost a signal to increase load drive capability, to isolate a signal to stop ground loops. More than 75000 combinations of process signal I/O, power input and mounting configuration are selectable. Additionally, M-System offers the broadest line of signal splitters available. Isolation amplifiers provide signal and power isolation for data acquisition components to protect them from noises present at remote devices.
For Resellers and High Volume Orders:
Please request a quote to obtain preferred pricing.
Features
- Being used for printed wiring board installation
- Built in surge protectors
- CE marking
- DC input model with optional fast response time
- Isolating between input and output, input and power
- Isolation between input and output up to 2000 V AC
- PC programmable models available
- Power 15 V DC
- Super-space-saving 12mm (0.47") width
- Universal AC/DC power input available
Specifications
- Construction: Hybrid IC
- Conversion gain: ×1 ±1 %
- DC Power input: Operational voltage range: Rating ±2 %; approx. 10 mA with no load; ripple 2 %p-p max
- Dielectric strength: 2000 V AC @ 1 minute (input or reference voltage source to output or power supply)
- Frequency characteristics: Approx. 1 kHz, -3 dB
- Housing Material: Flame-resistant resin (black)
- Insulation resistance: Greater than or equal to 100 M Omega with 500 V DC
- Isolation: Input or reference voltage source to output or power supply
- Line voltage effect: ±0.05 % over voltage range
- Linearity: ±0.05 %
- Mounting: Soldering to the printed wiring board
- Operating humidity: 30 to 90 %RH (non-condensing)
- Operating temperature: 0 to 60°C (32 to 140°F)
- Response time: Less than or equal to 450 µsec. (0 – 90 %)
- Temp. coefficient: Offset drift 40 ppm/°C; Span drift 50 ppm/°C
- Weight: 20 g (0.71 oz)
Applications
- None Available
Aliases